Rockwell-automation 1760-DNET Pico DeviceNet Communications Module Use Instrukcja Użytkownika Strona 90

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 168
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 89
Publication 1760-UM003A-EN-P - September 2005
7-10 Pico GFX Control Commands
Example
Data 1 = F8, Data 2 = FF l In the Pico-NET network, the three stations
are present with the NET IDs 1, 2, 3
Read local inputs: IW0
This command string enables you to read the local inputs of the Pico
GFX. The relevant input word is stored in Intel format.
Table 6.80 Telegram Structure
Byte Meaning Value (hex), sent by
Master Slave Master Slave
Attribute ID: Read 91
0 Response:
Read successful C2
Command rejected C0
01Len 02 02
1 2 Type 01 01
2 3 Index 00 00
3 4 Data 1 (Low Byte) 00 Table 6.81
4 5 Data 2 (High Byte) 00 Table 6.81
5 – 6 6 – 7 Data 3 – 4 00 00
Table 6.81 Byte 4 to 5: Data 1 to 2
Data 1 Bit76543210
I1 0/1
I2 0/1
.. ..
I8 0/1
Data 2 Bit76543210
I9 0/1
I10 0/1
.. ..
I16 0/1
Przeglądanie stron 89
1 2 ... 85 86 87 88 89 90 91 92 93 94 95 ... 167 168

Komentarze do niniejszej Instrukcji

Brak uwag