Publication 1760-UM002B-EN-P - March 2005
Wiring with Pico GFX-70 4-41
Figure 4.25 Pico GFX-70 circuit diagram with analog value comparators
Parameter display and parameter set for analog value comparators:
Inputs
The function block inputs >I1, >F1, >I2, >F2, >OS and >HY can have the
following operands:
Constants
Markers MD, MW, MB
Analog inputs IA01 to IA04
IA01: terminal I7
IA02: terminal I8
IA03: terminal I11
IA04: terminal I12
Analog output QA01
Actual value
QV> of another function block
I 01----A 01Q1-----------------[ Q 01
I 02--
|
-A 02Q1-----------------S Q 02
|
-A 03Q1-----------------R Q 03
A 02 GT +
>I1
>F1
>I2
>F2
>OS
>HY
A 02 Function block analog value comparator number 02
GT Greater than mode
+ Appears in the parameter display
>I1 Comparison value 1
>F1 Gain factor for
>I1 (>I1 = >F1 x value)
>I2 Comparison value 2
>F2 Gain factor for
>I2 (>I2 = >F2 x value)
>OS Offset for the value of
>I1
>HY Switching hysteresis for value >I2 (Value HY applies to positive and negative
hysteresis.)