Rockwell-automation 1760-xxxx Pico GFX-70 Controllers User Manual Instrukcja Użytkownika Strona 251

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 400
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 250
Publication 1760-UM002B-EN-P - March 2005
Wiring with Pico GFX-70 4-141
Inputs
The function block inputs >I1 and >I2 can have the following operands:
Constants
Markers MD, MW, MB
Analog inputs IA01 to IA04
IA01: terminal I7
IA02: terminal I8
IA03: terminal I11
IA04: terminal I12
Analog output QA01
Actual value
QV> of another function block
Actual Value QV>
The actual valueQV> can be assigned the following operands:
Markers MD, MW, MB
Analog output QA01
Table 4.65 Time Range
Parameter Time range and setpoint time Resolution
S 000.000 Seconds, 0.005 to 999.995s for constants and
variable values
5 ms
M:S 00:00 Minutes: Seconds 00:00 to 99:59 only for constants
and variable values
1 s
H:M 00:00 Hours: Minutes, 00:00 to 99:59 only for constants
and variable values
1 min.
IMPORTANT
Minimum time setting:
0.005 s (5 ms).
If a time value is less than the Pico GFX-70 cycle time, the
elapsed time will only be recognized in the next cycle.
Przeglądanie stron 250
1 2 ... 246 247 248 249 250 251 252 253 254 255 256 ... 399 400

Komentarze do niniejszej Instrukcji

Brak uwag