Rockwell-automation 1760-xxxx Pico GFX-70 Controllers User Manual Instrukcja Użytkownika Strona 60

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 400
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 59
Publication 1760-UM002B-EN-P - March 2005
2-26 Installation
Set Point Potentiometer
Figure 2.27 Set Point potentiometer, set point potentiometer with upstream resistor
Use a potentiometer with a resistance of greater than or equal to1 k, e.g. 1 k,
0.25W.
Temperature Sensor, Brightness Sensor, 20 mA Sensor
Figure 2.28 Temperature sensor, brightness sensor, 20 mA sensor
4 to 20 mA (0 to 20 mA) sensors can be connected using an external 500
resistor.
The following values apply:
4 mA = 1.9V
10 mA = 4.8V
20 mA = 9.5V
(according to U = R x I = 478 x 10 mA ~ 4.8V)
L01–
> 1 A
L01+
I1 I3 I4 I7 I8 I9 I10
L02+
I2 I5 I6 I11
I12
0 V
+12 V
H
h
1.3 kO/0.25 W
1 kO/0.25 W
+24V 0V 0V
L01–
> 1 A
L01+
I1 I3 I4 I7 I8 I9 I10
L02+
I2 I5 I6 I11
I12
+24V 0V 0V
0...10 V
0 V
+12 V
h
H
+24 V H
0 V
Out
0...10 V
–35...55 ˚C
a
500 O
4...20 mA
Przeglądanie stron 59
1 2 ... 55 56 57 58 59 60 61 62 63 64 65 ... 399 400

Komentarze do niniejszej Instrukcji

Brak uwag