Publication 1760-UM002B-EN-P - March 2005
4-106 Wiring with Pico GFX-70
Function of the GET Function Block
Figure 4.44 Signal diagram of the GET function block
1: GT..Q1
2: value on GT..QV>
Seven-Day Time Switch
Pico GFX-70 is equipped with a real-time clock which you can use in the
circuit diagram as a 7-day time switch and a year time switch.
Pico GFX-70 provides 32 seven-day time switches HW01 to HW32 for a total
of 128 switching times.
Each time switch has four channels which you can use to set four on and off
times. The channels are set via the parameter display.
The time is backed up in the event of a power failure and continues to run,
although the time switch relays will no longer switch. The contacts are kept
open when de-energized. Refer to General on page A-1 for information on the
buffer time.
Wiring of a 7-Day Time Switch
A 7-day time switch is integrated into the circuit diagram as a contact.
IMPORTANT
The GET function blocks are assigned the value 0 when the
power supply is switched on.
IMPORTANT
The procedure for setting the time is described under Setting
Date, Time and Daylight Savings Time on page 7-11.
1