154 Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Chapter 3 Drive Port 0 Parameters
Drive (Port 0) Diagnostics File
File
Group
No. Display Name
Full Name
Description
Values
Read-Write
Data Type
DIAGNOSTICS
Status
930 Speed Ref Source
Speed Reference Source
Indicates the currently selected source for value displayed in P593 [Limited Spd Ref].
The Speed Reference Source displays the parameter number that is supplying the speed
reference. For example, if Speed Reference Source contains the value 546, then P546
[Spd Ref A Stpt] is the source of the speed reference.
Default:
Min/Max:
0
0 / 159999
RO 32-bit
Integer
931 Last StartSource
Last Start Source
Displays the source that initiated the most recent start sequence. All bits in this
parameter are refreshed each time the drive receives a start command.
Default:
Options:
0 = Read Only
0 = “Pwr Removed”
1-6 = “Port 1-6”
7 = “Digital In
8 = “Sleep”
9 = “Jog”
10 = “Profiling”
11 = “AutoRestart”
12 = “Pwr Up Start
13 = “Fault”
14 = “Enable
15 = “Autotune
16 = “Precharge
17 = “Safety
18 = “Fast Stop
19 = “Port 13”
20 = “Port 14”
RO 32-bit
Integer
932 Last Stop Source
Last Stop Source
Displays the source that initiated the most recent stop sequence. All bits in this
parameter are refreshed each time the drive receives a stop command.
Default:
Options:
0 = Read Only
0 = “Pwr Removed”
1-6 = “Port 1-6”
7 = “Digital In
8 = “Sleep”
9 = “Jog”
10 = “Profiling”
11 = “AutoRestart”
12 = “Pwr Up Start
13 = “Fault”
14 = “Enable
15 = “Autotune
16 = “Precharge
17 = “Safety
18 = “Fast Stop
19 = “Port 13”
20 = “Port 14”
RO 32-bit
Integer