Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 61
Commissioning Chapter 3
Verify Operation of DCS Input and Output Signals
Figure 17 - Status Indicators
Table 9 - Drive to DCS
Signal Name Terminal Number HMI Status Terminal Open Terminal Closed
MVPRE-Closed CB 901-902 Allowed Red Grey
MV CLOSING 903-904 MVClosd Red Grey
Warning 905-906 Warning Red Grey
Fault 907-908 Warning Red Grey
Drive running 909-910 Running/Connect Red Grey
Drive STOP 911-912 Running/Connect Red Grey
READY 913-914 Ready Red Grey
DCS control 915-916 Remote Red Grey
Local Grey Red
Table 10 - 4-20 mA
Output Current 925-926 Motor Current 0-Rated Current
Output Frequency 927-928 Actual Frequency 0-Rated Frequency