Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 47
Commissioning Chapter 3
6. Press , and press to confirm the operation in the
Reset Drive? dialog box.
Wait until the Ready status indicator is red before starting another
simulation.
Simulate a Transformer Cabinet Main Cooling Fan Fault
1. Open the LV door of the Isolation Transformer cabinet.
2. Turn the first motor control circuit breaker (Q10), controlling the
Isolation Transformer Cabinet Main Cooling Fans (one per fan), to the
OFF position.
TIP
The circuit breakers for the main cooling fans for the entire drive are located
here.