
Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 77
No-load Test Chapter 4
3. Press , and press in the Start Drive? dialog box to
confirm operation.
4. Observe the direction of motor rotation.
If motor rotating direction is incorrect:
a. Press .
b. Open the Input Circuit Breaker.
c. Perform the Lockout and Tagout procedures.
d. Verify that medium voltage is not present in the drive and in the
motor’s cable connection box by using a hot stick.
e. Swap any two cables in the motor’s cable connection box.
f. Repeat Close Input Circuit Breaker
on page 75.
If the motor rotating direction is correct, continue to step 5.
When the drive is ≤0.5 Hz, the “Connect” light will be illuminated. When the
speed of the drive surpasses 0.5 Hz, the “Connect” and “Running” lights will be
red.
Komentarze do niniejszej Instrukcji