Rockwell Automation Publication 6000-IN007A-EN-P - October 2014 63
Commissioning Chapter 3
Press to enter password details. Press when finished.
3. Press to login.
4. Press , and press .
5. Press the P007 parameter field to enter the number of power cells per
phase, and press .
6. Press the P224 parameter field.
7. Change the value from 120 to 80. Press , and press .
8. Press to exit P Parameter Settings
, to confirm
Setup has logged out, and to return to the Main Interface
Screen.
WARNING: Do NOT press Reset. This will reset all factory-set parameters.
WARNING: Remove the temporary jumper (X1-117, X1-119) in the LV Control
Cabinet, which was installed to enable the Control System Test.