64 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014
Chapter 3 Commissioning
Set Date and Time Zone
To access the Date and Time Zone settings, you must exit the PowerFlex 6000
HMI to Windows CE.
Access T Parameters
1. Press from the Main Interface Screen.
2. Press under Parameter Access Level.
The Setup Login dialog box appears. Press .
3. Enter the User and Password details.
4. Press to login.
5. Once logged in, press .
6. Press in the Setup Parameter Type
.
7. Press the T10 parameter input field. Enter “555” and press .
8. Press and to confirm.
It will take 3...5 minutes to shutdown.