68 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014
Chapter 4 No-load Test
Energize Drive Control Circuit
The “Energize Control Circuit” process is already described on page 32. For the
“Energize Drive Control Circuit” procedure, repeat the process in the same
sequence, without the requirements of taking voltage measurements.
1. Close circuit breaker Q1.
2. Start UPS. Press and hold the ON button for approximately 3 seconds.
3. Close circuit breakers Q2, Q3, Q5, and Q6 in the LV Control Panel.
4. Close circuit breakers Q4 and Q7 in the Isolation Transformer Cabinet LV
Panel.
Configure P and T Parameters
Set the P parameters and T parameters as shown in Table 12.
This table outlines the specific parameters that must be checked and/or
modified. Parameters that must be modified are outlined in the Instruction
column. All other parameters listed must be verified. For special functions or
actions which are not listed here, but are commonly performed while
commissioning a drive, see Special Function Parameter Settings
on page 87.
TIP
See Set P Parameters to Enable Testing on page 37 for information on how to
access and change parameters.
Table 12 - Setup and R&D Parameters
P
Parameter
Description Default Modify
Root
(1)
Min.
Value
Max.
Value
Login
Level
Instruction
P004 Command Source
0: Communication Port
1: Other Sources
0OFF01Setup
P007 Number Of Power Cells Per Phase 9 ON 0 9 Setup Set to 0 for Control System Check. Afterwards, set to actual value
according to Electrical Drawings
P008 Motor Rotation Direction Under Local Control
1: Forward
0: Reverse
1OFF01Setup
P009 Motor Rotation Direction Command
Selection
0: Local
1: DCS
0OFF01Setup
P024 Stop Method
0: Ramp Down
1: Coast Stop
0ON01R&D
P040 Safe Start Condition
0: Zero Frequency Command Required
1: Frequency Command Allowed
1OFF01Setup
P089 Skip Frequency Enable
0: Disable
1: Enable
0ON01R&D
P090 Skip Frequency 1 Lower Limit 0 ON 0 75 R&D