Rockwell Automation Publication IASIMP-QS034A-EN-P - October 2012 197
System Commissioning Chapter 6
Download Applications
This section provides general steps for downloading the RSLogix 5000 project to the controller, and
downloading the FactoryTalk View project to the PanelView Plus terminal.
Download RSLogix 5000 Software Project File to the Logix Controller
1. Open your RSLogix 5000 project file.
2. From the Communications menu, choose Who Active.
The Who Active dialog box opens.
3. Browse to and select your Logix
controller and click Set Project Path.
4. Verify the key switch on your controller
module is in the REM (remote) position.
5. Click Download.
The Download dialog box opens.
IMPORTANT
The download steps assume controller power and communication wiring is connected, controller power is applied and
RSLinx communication driver is configured. See Appendix D
for more information on these topics.