Rockwell-automation IASIMP Computer Numerical Control (CNC) Machining Instrukcja Użytkownika Strona 207

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 278
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 206
Rockwell Automation Publication IASIMP-QS034A-EN-P - October 2012 207
System Commissioning Chapter 6
Controller to Device Communication
Verify controller to device communication by observing the indicators on the controllers communication
module and the devices in the controller’s I/O tree.
1. Observe the controllers communication module.
Refer to the user manual for the specific module you are using.
2. Open your RSLogix 5000 project, go online with the
controller, and observe the devices in the I/O tree.
A device with a yellow exclamation mark (!)
indicates a fault. The fault could be a
configuration fault, a device fault, or a
communication fault. View the quick pane in the
Controller Organizer to determine fault.
3. From the HMI, open the faceplate for the
individual CNC Device.
Verify that the Comms. Ok status is green. The
controller is monitoring a heart beat signal being
produced by the CNC. As long as the controller
detects a continuing transition, the status remains
green; otherwise, the status is red.
Status Indicator Status
OK Solid green
LNK1 Flashing green (indicates network activity)
LNK2 Off (flashing green if in a Device Level Ring configuration)
OK
LNK2
LNK1
1756-EN2TR
EtherNet/IP
Module
Przeglądanie stron 206
1 2 ... 202 203 204 205 206 207 208 209 210 211 212 ... 277 278

Komentarze do niniejszej Instrukcji

Brak uwag