Rockwell Automation Publication IASIMP-QS034A-EN-P - October 2012 89
GuardLogix Configuration Chapter 4
Configure Ethernet Module for your HMI Terminal and CNC Modules
1. Expand I/O Configuration in the Controller
Organizer.
2. Right-click I/O Configuration and choose New
Module.
The Select Module Type dialog box opens.
3. Expand the Communications
category and select your 1756-series
Ethernet module.
In this example, the 1756-EN2TR
module is selected.
4. Click Create.
The New Module dialog box opens.
5. Configure the new module.
a. Enter the module Name.
b. Enter the Logix EtherNet/IP
module slot (leftmost slot = 0).
c. Select an Ethernet Address option.
In this example, the Private Network
address is selected.
d. Enter the address of your
EtherNet/IP module.
In this example, the last octet of the
address is 10.
6. Click Change in the Module
Definition area.
The Module Definition dialog box opens.
TIP
For systems communicating to a
FANUC CNC over an EtherNet/IP
network, a 1756-EN2x or
1756-EN3x module is required.