This means that although the actual data is being updated, the meter port output will change only
when the data changes by 32 or more counts. This level of granularity might be acceptable if the
range of the data were actually 8190 counts, but might not be acceptable if the data range is only
4095 counts. If the programmer had assigned the limits +/-1024, the D/A output step change would
be only 8 counts: 2048/255 = 8.
1001
Initiate Change in Setup Register
Hex Value:
N/A
Sug. Var. Name:
N/A
Range:
N/A
Access:
Read/Write
UDC Error Code:
N/A
LED:
N/A
Description: Set this register equal to a non-zero value to store the new setup register configurations
in UDC memory. You must use this register whether you are changing the meter port setup via an
application task or via l/O Monitor.
3-43