Publication 2098-RM003A-EN-P October 2001
2-96 Command Reference
Maximum Encoder Output Frequency
Format: :aa0EFfddcc<cr>
Parameter
Code:
0x0EF
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x03 = EEPROM Write Error
0x05 = Data Above Maximum
0x08 = Invalid Function Code
Data Fields: dd Maximum encoder output frequency, where:
0 = 500kHz
1 = 1 MHz
2 = 4 MHz
3 = 8 MHz.
Minimum
Value:
0x00 0x00
Maximum
Value:
0x03 0x03
Default: 0x00 0x00