Publication 2098-RM003A-EN-P October 2001
Command Reference 2-17
Communications
Commands
Baud Rate
Format: :aa050fddcc<cr>
Parameter
Code:
0x050
Valid Function
Codes:
0x0 = Read Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x03 = EEPROM Write Error
0x05 = Data Above Maximum
0x08 = Invalid Function Code
Data Fields: dd Baud rate code, where:
0x00: 1200 baud
0x01: 2400 baud
0x02: 4800 baud
0x03: 9600 baud
0x04: 19200 baud
0x05: 38400 baud
Minimum
Value:
0x00
Maximum
Value:
0x05
Default: 0x05