Publication 2098-RM003A-EN-P October 2001
2-22 Command Reference
Analog Current Scale
Format: :aa119fddddcc<cr>
Parameter
Code:
0x119
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x03 = EEPROM Write Error
0x04 = Data Below Minimum
0x05 = Data Above Maximum
0x08 = Invalid Function Code
Data Fields: dddd Analog current scale, in units of percentage of the
minimum of the motor intermittent current rating
and drive intermittent current rating, per 10 Volts.
Minimum
Value:
-200 -200
Maximum
Value:
200 200
Default: 100 100