
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012 125
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
User I/O Configuration Group
Str Net FltValue
This parameter determines how the
starter will be commanded in the
event of a fault. State the Starter will
go to on a Net Flt if Parameter 26 (Str
Net FltState) = 0 (Goto Fault Value).
0 = OFF
1 = ON
Parameter Number 27
Access Rule GET
Data Type BOOL
Group Starter Protection
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
Str Net IdlState
This parameter in conjunction with
Parameter 29 (Str Net IdlValue)
defines how the starter will respond
when a network is idle as determined
by Parameter 29.
0 = Goto Idle Value
1 = Hold Last State
Parameter Number 28
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
Str Net IdlValue
This parameter determines the state
that starter assumes when the
network is idle and Parameter 28 (Str
Net IdlState) is set to “0”.
0 = OFF
1 = ON
Parameter Number 29
Access Rule GET
Data Type BOOL
Group Starter Protection
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
Anti-bounce On Delay
This parameter allows the installer to
program a time duration before an
input is reported “ON” (Anti-bounce).
Parameter Number 30
Access Rule GET/SET
Data Type UINT
Group User I/O Config.
Units ms
Minimum Value 0
Maximum Value 65
Default Value 0
Komentarze do niniejszej Instrukcji