78 Rockwell Automation Publication 280E-UM001B-EN-P - July 2012
Chapter 4 Product Commissioning
E-mail triggers:
when a trip occurs
when a trip is cleared
when a warning occurs
when a warning is cleared
Note: “Cleared Event” e-mails will only be sent when all events have been cleared
and if a trip event e-mail has previously been sent. For example, if the device is
configured to send e-mails when a phase loss trip and an overload trip is detected,
no e-mail will be sent when both the overload and the phase loss is cleared.
The following is an example trip e-mail:
Subject: ArmorStart 281E, 0.5
2.5 A, 24V DC has detected a trip.
Body:
Trip Ty p e : O v er load
Trip Info: Load has drawn excessive current based on the trip
class selected.
Device Name: ArmorStart 281E, 0.5
2.5 A, 24V DC
(From Identity Object)
Device Description: Lift conveyor on-machine motor starter
(From E-mail Config web page)
Device Location: Customer Plant
(From E-mail Config web page)
Contact Info: Joe Schmo
(From E-mail Config web page)
Device Connections
The device will support both scheduled (Class 1) and unscheduled (Class 3 &
UCMM) CIP connections. A maximum of two Class 1 CIP connections (one
exclusive owner and one listen only) are supported, one per PLC. Six Class 3 CIP
connections are supported.