Rockwell Automation Publication 280E-UM001B-EN-P – July 2012 147
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
User I/O Configuration Group
Anti-bounce On Delay
This parameter allows the installer to
program a time duration before being
reported “ON” (Anti-bouce).
Parameter Number 30
Access Rule GET/SET
Data Type UINT
Group User I/O Config.
Units ms
Minimum Value 0
Maximum Value 65
Default Value 0
Anti-bounce OFF Delay
This parameter allows the installer to
program a time duration before being
reported “OFF” (Anti-bouce).
Parameter Number 31
Access Rule GET/SET
Data Type UINT
Group User I/O Config.
Units ms
Minimum Value 0
Maximum Value 65
Default Value 0
In Sink/Source
This parameter allows the installer to
program the inputs to be sink or
source.
0 = Sink
1 = Source
Parameter Number 32
Access Rule GET/SET
Data Type BOOL
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
OutA Pr FltState
This parameter in conjunction with
Parameter 34 (OutA Pr FltValue)
defines how Output A will respond
when a trip occurs.
0 = Goto PrFlt Value
1 = Ignore PrFlt
When set to “1”, Output A continues to
operate as command via the network.
When set to “0”, Output A will open or
close as determined by the setting in
Parameter 34.
Parameter Number 33
Access Rule GET/SET
Data Type BOOL
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0