300 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Appendix B CIP Information
The table below lists Fault Codes, Fault Text, and Fault Help Strings for VFD
units.
36 Fault 36
37 Fault 37
38 Fault 38
39 Fault 39
40 Unknown Fault
41 Fault 41
42 Fault 42
43 Fault 43
44 Fault 44
45 Fault 45
Table 50 Bulletin 284E
Fault Code Fault Text Help Text
1 Hdw Short Ckt The built in 140M Circuit Breaker has tripped.
2Fault 2
3 Motor Overload The Load has drawn excessive current.
4 Drive Overload 150% load for 1 min. or 200% load for 3 sec. exceeded
5 Phase U to Gnd A Phase U to Ground fault detected between drive and motor.
6 Phase V to Gnd A Phase V to Ground fault detected between drive and motor.
7 Phase W to Gnd A Phase W to Ground fault detected between drive and motor.
8 Phase UV Short Excessive current detected between phases U and V.
9 Phase UW Short Excessive current detected between phases U and W.
10 Phase VW Short Excessive current detected between phases V and W.
11 Ground Fault A current path to earth ground at one or more output terminals.
12 Stall The drive is unable to accelerate the motor.
13 Control Pwr Loss Indicates the loss of control power. This fault can be disabled.
14 Control Pwr Fuse The Control Power Fuse has blown. Remove power and replace fuse.
15 Input Short Flags a shorted sensor, input device, or input wiring mistake.
16 Output Fuse The Output Fuse has blown. Remove all power and replace the fuse.
17 Over Temp Indicates the operating temperature has been exceeded.
18 Heatsink OvrTmp The Heatsink temperature exceeds a predefined value.
19 HW OverCurrent The drive output current has exceeded the hardware limit.
20 SW OverCurrent Programmed parameter 198 (SW Current Trip) has been exceeded.
21 A3 Power Loss Unswitched (A3) Power was lost or dipped below the 12V DC threshold.
22 Internal Comm Communication with the internal Power Flex drive has been lost.
23 Drive Comm Loss The RS485 port on the internal Power Flex stopped communicating.
Table 49 - Bulletin 280E/281E
Fault Code Fault Text Help Text