180 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Comm Loss Time
Sets the time that the drive remain in
communication loss before
implanting the option selected in
Parameter 205 (Comm Loss Action).
Parameter Number 206
Related Parameters 115, 205
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units 0.1 sec
Minimum Value 0.1 sec
Maximum Value 60.0 sec
Default Value 15.0 sec
Slip Hertz @ FLA
Compensates for the inherent slip in
an induction motor. This frequency is
added to the commanded output
frequency based on motor current.
Parameter Number 214
Related Parameters 133
Access Rule GET/SET
Data Type UINT
Group Drive Advanced Setup
Units 0.1 Hz
Minimum Value 0.0 Hz
Maximum Value 10.0 Hz
Default Value 2.0 Hz
Process Time Lo
Scales the time value when the drive
is running at Parameter 134
(Minimum Freq). When set to a value
other than zero, Parameter 110
(Process Display) indicates the
duration of the process.
Parameter Number 215
Related Parameters 110, 134
Access Rule GET/SET
Data Type UINT
Group Drive Advanced Setup
Units Hz
Minimum Value 0.00
Maximum Value 99.99
Default Value 0.00
Process Time Hi
Scales the time value when the drive
is running at Parameter 135
(Maximum Freq). When set to a value
other than zero, Parameter 110
(Process Display) indicates the
duration of the process.
Parameter Number 216
Related Parameters 110, 135
Access Rule GET/SET
Data Type UINT
Group Drive Advanced Setup
Units Hz
Minimum Value 0.0
Maximum Value 99.99
Default Value 0.00