Rockwell Automation Publication 280E-UM001B-EN-P – July 2012 299
CIP Information Appendix B
The table below lists Fault Codes, Fault Text, and Fault Help Strings for DOL
and Reversers.
Table 49 - Bulletin 280E/281E
Fault Code Fault Text Help Text
1 Hdw Short Ckt The built in 140M Circuit Breaker has tripped.
2 Sfw Short Ckt The wire protection algorithm detected an unsafe current surge.
3 Motor Overload Load has drawn excessive current based on trip class selected.
4 Fault 4 —
5 Phase Loss Indicates missing supply phase. This fault can be disabled.
6 Fault 6 —
7 Fault 7 —
8 Fault 8 —
9 Fault 9 —
10 Fault 10 —
11 Fault 11 —
12 Fault 12 —
13 Control Pwr Loss Indicates the loss of control power. This fault can be disabled.
14 Control Pwr Fuse The Control Power Fuse has blown. Remove power and replace fuse.
15 Input Short Flags a shorted sensor, input device, or input wiring mistake.
16 Output Fuse The Output Fuse has blown. Remove all power and replace the fuse.
17 Over Temp Indicates the operating temperature has been exceeded.
18 Fault 18 —
19 Phase Imbalance Indicates an imbalanced supply voltage.
20 Fault 20 —
21 A3 Power Loss Unswitched (A3) Power was lost or dipped below the 12V DC threshold.
22 Internal Comm Communication with an internal component has been lost.
23 Fault 23 —
24 Fault 24 —
25 Fault 25 —
26 Fault 26 —
27 MCB EEPROM This is a major fault which renders the ArmorStart inoperable.
28 Base EEPROM This is a major fault which renders the ArmorStart inoperable.
29 Fault 29 —
30 Wrong Base The ArmorStart controller is connected to the wrong base type.
31 Wrong CTs This is a major fault which renders the ArmorStart inoperable.
32 Fault 32 —
33 Fault 33 —
34 Fault 34 —
35 Fault 35 —