Rockwell-automation 284E ArmorStart with EtherNet/IP - User Manual Instrukcja Użytkownika Strona 298

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 348
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 297
298 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Appendix B CIP Information
The following class attributes are supported:
Four instances of the DPI Fault Object are supported. The have the following
instance attributes:
The following services are supported:
Attribute ID Access Rule Name Data Type Value
1 Get Class Revision UINT 1
2 Get Number of Instances UINT 4
3 Get Fault Cmd Write USINT 0 = NOP, 1 = Clear Fault, 2 = Clear Flt Queue
4 Get Fault Instance Read UINT
The instance of the Fault Queue Entry containing
information about the Fault that tripped the Device.
6 Get Number of Recorded Faults UINT The number of Faults recorded in the Fault Queue.
Attribute ID Access Rule Name Data Type Value
0 Get Full/All Info Struct of:
Fault Code UINT See table below.
Fault Source Struct of:
DPI Port Number USINT 0
Device Object Instance USINT 0x2c
B Fault Text BYTE[16] See table below.
Fault Time Stamp Struct of:
Timer Value ULDINT
Timer Description WORD
Help Object Instance USINT
—— Fault Data
1GetBasic Info Struct of:
Fault Code UINT See table below.
Fault Source Struct of:
DPI Port Number USINT 0
Device Object Instance USINT 0x2C
Fault Time Stamp Struct of:
Timer Value ULINT
Timer Description WORD
3 Get Help Text STRING See table below.
Service Code
Implemented for:
Service NameClass Instance
0x0E Yes Yes Get_Attribute_Single
0x10 Yes No Set_Attribute_Single
Przeglądanie stron 297
1 2 ... 293 294 295 296 297 298 299 300 301 302 303 ... 347 348

Komentarze do niniejszej Instrukcji

Brak uwag