Rockwell-automation 284E ArmorStart with EtherNet/IP - User Manual Instrukcja Użytkownika Strona 161

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 348
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 160
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012 161
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
Motor NP Hertz
Set to the motor nameplate rated
frequency.
Parameter Number 132
Related Parameters 184, 185…187, and 190
Access Rule GET/SET
Data Type UINT
Group Drive Setup
Units 1 Hz
Minimum Value 15
Maximum Value 400
Default Value 60 Hz
Motor OL Current
Set to the maximum allowable
current. The drive fault on an F7
Motor Over load if the value of this
parameter is exceeded by 150%
for 60 s.
Parameter Number 133
Related Parameter
155, 189, 190, 198, 214, 218,
260…261
Access Rule GET/SET
Data Type UINT
Group Drive Setup
Units 0.1 A
Minimum Value 0.0
Maximum Value Drive rated amps x 2
Default Value Based on Drive Rating
Minimum Freq
Sets the lowest frequency the drive
will output continuously.
Parameter Number 134
Related Parameter
101, 102, 113, 135, 185…187,
260, 261
Access Rule GET/SET
Data Type UINT
Group Drive Setup
Units 0.1 Hz
Minimum Value 0.0
Maximum Value 400
Default Value 0.0
Stop drive before changing this
parameter.
O
Przeglądanie stron 160
1 2 ... 156 157 158 159 160 161 162 163 164 165 166 ... 347 348

Komentarze do niniejszej Instrukcji

Brak uwag