Rockwell Automation Publication 280E-UM001B-EN-P – July 2012 187
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
Parameters 240…247 are only active if Parameter 138 (Speed Reference) is set
to “6” (StpLogic).
These parameters can be used to create a custom profile of frequency commands.
Each step can be based on time, status of a Logic input, or a combination of time
and the status of a Logic input.
Digits 0…3 for each (StpLogic x) parameter must be programmed according
to the desired profile. Refer to Tables 25, 26 and 27.
A Logic input is established by setting a digital input, Parameters 151…154
(Digital In x Sel), to 23 (Logic In1) and/or 24 (Logic In2).
A time interval between steps can be programmed using Parameters 250…257
(StpLogic Time x). See Table24 for related parameters.
The speed for any step is programmed using Parameters 170…177 (Preset Freq x).
StpLogic 0 (240) (see Table25)
StpLogic 1 (241) (see Table25)
StpLogic 2 (242) (see Table26)
StpLogic 3 (243) (see Table27)
StpLogic 4 (244)
StpLogic 5 (245)
StpLogic 6 (246)
StpLogic 7 (247)
Stop drive before changing this parameter.
Parameter Number 240…247
Access Rule GET/SET
Data Type UINT
Group Drive Advanced Setup
Units —
Minimum Value 0001
Maximum Value baFF
Default Value 00F1
Table 24 - Parameters 240…257
StepLogic Parameter (Active
when
138 = 6 (StpLogic))
Related Preset Frequency
Parameter (Can be
activated independent of
StepLogic Parameters)
Related StepLogic Time Parameter
(Active when 240…247 Digit 0 or 1
are
set to 1, b, C, d, or E)
240 (StpLogic 0) 170 (Preset Freq 0) 250 (StpLogic Time 0)
241 (StpLogic 1) 171 (Preset Freq 1) 251 (StpLogic Time 1)
242 (StpLogic 2) 172 (Preset Freq 2) 252 (StpLogic Time 2)
243 (StpLogic 3) 173 (Preset Freq 3) 253 (StpLogic Time 3)
244 (StpLogic 4) 174 (Preset Freq 4) 254 (StpLogic Time 4)
245 (StpLogic 5) 175 (Preset Freq 5) 255 (StpLogic Time 5)
246 (StpLogic 6) 176 (Preset Freq 6) 256 (StpLogic Time 6)
247 (StpLogic 7) 177 (Preset Freq 7) 257 (StpLogic Time 7)