Instance 2 contains the following instance attributes.
The following common services are implemented for the Discrete Output Group
Object.
Control Supervisor Object
CLASS CODE 0x0029
No class attributes are supported.
A single instance (Instance 1) of the Control Supervisor Object is supported and
contains the following instance attributes.
Attribute ID Access Rule Name Data Type Value
3 Get Number of Instances USINT 4
4 Get Binding Array of UINT 5, 6, 7, 8
7 Get/Set Fault Action BOOL 0 = Fault Value Attribute, 1 = Hold Last State
8 Get/Set Fault Value BOOL 0 = OFF, 1 = On
9 Get/Set Idle Action BOOL 0 = Idle Value Attribute, 1 = Hold Last State
10 Get/Set Idle Value BOOL 0 = OFF, 1 = On
113 Get/Set Pr Fault Action BOOL 0 = Pr Fault Value Attribute, 1 = Ignore
114 Get/Set Pr Fault Value BOOL 0 = OFF, 1 = On
Service Code
Implemented for:
Service NameClass Instance
0x0E No Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
Attribute ID Access Rule Name Data Type Value
3 Get/Set Run 1 BOOL
These Run outputs also map to DOP
Instances 1 and 2
4 ➊ Get/Set Run 2 BOOL —
7 Get Running 1 BOOL —
8 ➊ Get Running 2 BOOL —
9 Get Ready BOOL —
10 Get Tripped BOOL —
12 Get/Set Fault Reset BOOL 0->1 = Trip Reset
100 Get/Set Keypad Mode BOOL 0 = Maintained, 1 = Momentary
101 Get/Set Keypad Disable BOOL 0 = Not Disabled, 1= Disabled