Configuring the Ultra3000 Drive Chapter 3
Understanding the Digital
Outputs Window
The Properties window for Digital Outputs looks like this
Use the Digital Outputs window to:
assign functions to digital outputs,
set both active and inactive brake delays,
monitor the status of digital outputs and the digital relay, and
open other windows where you can override the state of digital outputs
and the relay.
The following parameters are associated with this window:
Parameter Description
Output 1 – 4 The functions to be assigned to each digital output (1 – 4):
Note: If multiple functions are assigned to a digital output, the
output is active if any of the assigned functions would make it
active. The assignments are logically OR'd to determine the
output state.
At Home: An active state indicates that the position
command is equal to the Home Position.
At Index 0 Position: An active state indicates the commanded
motor position is equal to the position defined by Index 0.
This output functions only after the axis has been homed.
At Index 1 Position: An active state indicates the commanded
motor position is equal to the position defined by Index 1.
This output functions only after the axis has been homed.
Axis Homed: An active state indicates that the homing
routine has completed.
Brake: Used to control a motor brake. An active state
releases the motor brake. The Brake signal is the same as the
Drive Enabled signal, with the addition of the turn-on and
turn-off delays specified by the Brake Active Delay
and Brake
Inactive Delay.